Product Information
HAN: | 558064 |
Category: | Type 8041 - Insertion magnetic inductive flowmeter |
Nominal voltage: | 18,0 V - 36 V |
Temperature range: | 0,00 °C - 80,00 °C |
Measurement: | Flow rate |
Sensor type: | Magnetic inductive |
Output 1 digital type: | Transistor |
Gasket sensor/housing: | FKM (fluororubber) |
Sensor fitting material: | PVDF (Polyvinylidene fluoride) |
Fluid side seal: | FKM (Fluor rubber) |
Product Description
The electromagnetic flowmeter 8041 is made up of an electronic module and a sensor consisting of PVDF or stainless steel material. It has been designed to measure a flow rate of neutral and slightly aggressive fluids with a conductivity of more than 20 µS/cm in DN 06…DN 400 pipes. It is fitted with a 4…20 mA output, a pulse output and a relay output. The different parameters can be set by means of 5 DIP switches, a push-button and a 10-field LED bar graph. This flowmeter is available either with a G 2" connection with a PVDF sensor or, a G 2" or clamp connection with a stainless steel sensor which are designed for use with Type S020 Insertion fitting. The variant with a stainless steel sensor can be used in applications with higher pressures (PN 16) and higher temperatures (150 °C).
- Sensor without moving parts
- Flowmeter with On/Off control
- Application related calibration by Teach-In function
- Clean in place (CIP)
- FDA-compliant materials
Manufacturer according to GPSR
Christian Bürkert GmbH & Co. KG, Christian-Bürkert-Straße 13-17, 74653 Ingelfingen, Baden-Württemberg, Deutschland, info@burkert.com, https://www.buerkert.de